Maintenance Parts Pro is pleased to offer procurement options for Eaton Corporation part number AM3 A8AW 20A 10, a Circuit Breaker product we carry that is listed with the NSN 5925-01-341-0957 for seamless identification. As this item is available for purchase today, be sure to fill out and submit the Request for Quote (RFQ) form on this page if you are interested in obtaining pricing information. All that we ask is that you share details like your budget, desired quantity, and expected fulfillment speed so that we can respond with the most fitting solutions for your comparisons.
Note : We Will Not Share Your Information To Any Third Parties.
Alongside streamlined quotation processes, we aim to support our customers by providing as much relevant listing information and data with product offerings as possible. For example, part number AM3 A8AW 20A 10 specifically traces back to Eaton Corporation through CAGE Code 74193, as well as belongs to the FSC [FSC] as per its NSN of 5925-01-341-0957. Referencing such details, you can locate and procure exact specifications with ease. With our various practices in mind, do not hesitate to request a quote on part number AM3 A8AW 20A 10 using our provided form.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-341-0957 Item PartTypeName: CIRCUIT BREAKER | 5925 | 013410957 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | ||||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
AM3-A8AW-20A-10 | 5 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.471 INCHES NOMINAL |
AKPX | POLE QUANTITY | 1 |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
THSD | THREAD SERIES DESIGNATOR | UNC |
ADAQ | BODY LENGTH | 2.500 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.150 INCHES NOMINAL |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CWJK | CASE MATERIAL | PLASTIC |
AAQL | BODY STYLE | SINGLE POLE TYPE |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.060 INCHES NOMINAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
ADAT | BODY WIDTH | 0.750 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.250 MINIMUM AT 200 PCT AND 2.500 MAXIMUM AT 200 PCT SINGLE LOCATION |
TTQY | TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |