Maintenance Parts Pro is pleased to offer procurement options for Eaton Corporation part number AM12MG3-1-50DC5, a Circuit Breaker product we carry that is listed with the NSN 5925-00-775-3614 for seamless identification. As this item is available for purchase today, be sure to fill out and submit the Request for Quote (RFQ) form on this page if you are interested in obtaining pricing information. All that we ask is that you share details like your budget, desired quantity, and expected fulfillment speed so that we can respond with the most fitting solutions for your comparisons.
Note : We Will Not Share Your Information To Any Third Parties.
Alongside streamlined quotation processes, we aim to support our customers by providing as much relevant listing information and data with product offerings as possible. For example, part number AM12MG3-1-50DC5 specifically traces back to Eaton Corporation through CAGE Code 74193, as well as belongs to the FSC [FSC] as per its NSN of 5925-00-775-3614. Referencing such details, you can locate and procure exact specifications with ease. With our various practices in mind, do not hesitate to request a quote on part number AM12MG3-1-50DC5 using our provided form.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-775-3614 Item PartTypeName: CIRCUIT BREAKER | 5925 | 007753614 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | ||||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
AM12MG3-50DC5 | 1 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | SINGLE POLE TYPE |
ADAQ | BODY LENGTH | 2.500 INCHES NOMINAL |
ADAT | BODY WIDTH | 0.750 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.611 INCHES NOMINAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 50.0 DC SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
AJEC | BOSS HEIGHT | 0.140 INCHES NOMINAL |
AKPX | POLE QUANTITY | 1 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1.0 AMPERES DC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.155 MINIMUM AT 200 PCT AND 0.600 MAXIMUM AT 200 PCT SINGLE LOCATION |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
CWJK | CASE MATERIAL | PLASTIC |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
If You’re Ever Looking for NSN parts Or Have an Aircraft On Ground Situation, Don’t forget That We offer Competitive Pricing and Guaranteed On-Time Delivery.
Request for Quote