Maintenance Parts Pro is pleased to offer procurement options for Eaton Corporation part number SPEC61-362M7-60A, a Circuit Breaker product we carry that is listed with the NSN 5925-00-201-7130 for seamless identification. As this item is available for purchase today, be sure to fill out and submit the Request for Quote (RFQ) form on this page if you are interested in obtaining pricing information. All that we ask is that you share details like your budget, desired quantity, and expected fulfillment speed so that we can respond with the most fitting solutions for your comparisons.
Note : We Will Not Share Your Information To Any Third Parties.
Alongside streamlined quotation processes, we aim to support our customers by providing as much relevant listing information and data with product offerings as possible. For example, part number SPEC61-362M7-60A specifically traces back to Eaton Corporation through CAGE Code 74193, as well as belongs to the FSC [FSC] as per its NSN of 5925-00-201-7130. Referencing such details, you can locate and procure exact specifications with ease. With our various practices in mind, do not hesitate to request a quote on part number SPEC61-362M7-60A using our provided form.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-201-7130 Item PartTypeName: CIRCUIT BREAKER | 5925 | 002017130 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | ||||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
320P112 | C | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AKPX | POLE QUANTITY | 2 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 60.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 160.000 MINIMUM AND 600.000 MAXIMUM ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | RESET |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 40.000 MINIMUM AT 200 PCT AND 125.000 MAXIMUM AT 200 PCT AND 12.000 MINIMUM AT 300 PCT AND 38.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 SCREW |
If You’re Ever Looking for NSN parts Or Have an Aircraft On Ground Situation, Don’t forget That We offer Competitive Pricing and Guaranteed On-Time Delivery.